NEC 625.40 · Homes

Dedicated circuits for EV chargers

An EV charger rated more than 16 A or more than 120 V needs its own individual branch circuit, unless an energy management system or a restricted adjustable setting lets several chargers share one.

Wiring diagram: Level 1 charger on a shared 15 or 20 A garage circuit; a charger over 16 A or 120 V on its own circuit; 40 A charger needs a 50 A breaker.
Several Level 2 chargers may share one circuit only under an energy management system or restricted adjustable settings in 625.42. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

Each outlet that supplies electric vehicle supply equipment (EVSE) rated more than 16 A or more than 120 V must be on an individual branch circuit. That covers typical Level 2 chargers. One circuit may feed several chargers only when they are managed under 625.42(A), an energy management system, or 625.42(B), adjustable current settings.

The code treats EV charging as a continuous load. Under 625.41 the breaker or fuse must be at least 125% of the charger's rating. For example, a charger rated 40 A needs a 50-A overcurrent device, with 8 AWG copper conductors at their 75°C ampacity or 6 AWG NM cable at its 60°C ampacity.

In the service and feeder load calculation, 220.57 counts each charger at 7,200 W (VA) or its nameplate rating, whichever is larger. That rule is not limited to homes.

On the job

  • A Level 1 charger that plugs into a standard 15- or 20-A garage receptacle no longer needs its own circuit under the 2023 NEC.
  • A Level 2 charger still needs an individual circuit unless an energy management system or an adjustable setting is used.
  • Your electrician should run a load calculation, counting the charger as 220.57 requires, before it goes in, to confirm the service can carry it.
Wall-mounted EV charger with a coiled cable beside a white electric car
Wall-mounted EV charger (representative stock photo).

Exceptions that matter

  • Several chargers may share one branch circuit when an energy management system under 625.42(A), or restricted-access adjustable settings under 625.42(B), limit the load.

What changed in 2023

The 2020 NEC required an individual circuit for every EV charging outlet; the 2023 edition applies the rule only above 16 A or 120 V and allows shared circuits under 625.42.

In California

For new construction, California's 625.1.1 adds the CALGreen EV requirements on top of this rule.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process