Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process
ServicesEV chargersFree toolsCode libraryWorkService areasAboutContact

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process

NEC 410.116 · Homes

Recessed lights and insulation (IC vs non-IC)

A recessed light that is not rated Type IC cannot have insulation above it or within 3 in. of its housing, wiring compartment or driver. Type IC fixtures are rated for contact with insulation.

Cross-section of recessed lights: Type IC may touch insulation; non-IC needs 3 in. clear to the housing and driver and no insulation above.
Before blowing in more attic insulation, check whether the recessed housings are IC rated. A non-IC can covered over has to be fixed. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

Recessed luminaires, often called can lights or downlights, come in two broad types. Type IC fixtures are rated for contact with thermal insulation. Non-IC fixtures are not, and the code keeps insulation away from them.

Under 410.116(B), thermal insulation may not be installed above a non-IC recessed luminaire, or within 3 in. (75 mm) of its enclosure, wiring compartment, ballast, transformer, LED driver or power supply.

Under 410.116(A), a non-IC fixture's recessed parts must be at least ½ in. (13 mm) from combustible material, though its supports and trim may touch the finished surface; a Type IC fixture may touch combustibles. Under 410.116(C), a fixture marked for non-fire-rated installations may not go in fire-rated construction, and a recessed fixture in fire-resistant construction must be listed for it, sit in a listed enclosure, or be installed per a tested fire resistance-rated assembly.

On the job

  • Non-IC fixtures covered by attic insulation do not comply. Either the 3 in. clearance is kept open with no insulation on top, or an IC-rated fixture is used.
  • Before insulation is added to an existing attic, it is worth confirming whether the recessed housings are IC-rated.
Kitchen with a vaulted ceiling of recessed lights and pendants over an island
Recessed lights in a kitchen ceiling (representative stock photo).

Exceptions that matter

  • Type IC luminaires, which are rated for contact with insulation, are exempt from the 3 in. insulation clearance.

In California

For new construction, the 2025 California Energy Code §150.0(k)1C requires recessed ceiling downlights to have no screw-base sockets, an airtight label (under 2.0 cfm at 75 Pa per ASTM E283) and a gasket or caulk seal to the ceiling (these two items do not apply to luminaires marked for fire-rated installations or in noninsulated ceilings), and to meet the CEC 410.116 clearances. Under §150.0(k)1D, lamps in enclosed or recessed fixtures must meet the JA8 elevated-temperature requirements, including marking.

Related sections

  • NEC 410.115
  • NEC 410.117

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process