NEC 334.30 · Homes

Stapling and supporting NM cable

NM cable must be secured at least every 4½ ft and within 12 in. of each box or cabinet it enters, using staples, straps or similar fittings that do not damage the cable.

Diagram of NM cable stapling: within 12 in. of each box, staples 4½ ft max apart, 18 in. max of cable to the first staple; no edge or crushing staples.
A first staple too far from the box is a common correction, along with over-driven staples and flat cable stapled on edge. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

NM cable must be secured with staples, cable ties listed for securement, straps, hangers or similar fittings that do not damage the cable. Fasteners can be no more than 4½ ft (1.4 m) apart.

The cable must be secured within 12 in. (300 mm) of every point where it enters a box, cabinet or fitting, and the cable between that entry and the nearest support may not be longer than 18 in. (450 mm). Flat cable may not be stapled on edge. Cable inside a protective raceway does not need to be secured within the raceway.

In runs that are not vertical, cable through holes or notches in framing counts as supported if those supports are no more than 4½ ft apart and the cable is fastened within 12 in. of each box or termination.

On the job

  • A common correction is the first staple too far from the box. It must be within 12 in., and the cable from the box to that support no longer than 18 in.
  • Over-driven staples that crush the cable jacket, and flat cable stapled on its edge, are also frequent corrections.
Interior of a wood-framed house at the rough-in stage
Wood framing at rough-in (representative stock photo).

Exceptions that matter

  • Cable may be unsupported where it is fished between access points through concealed spaces in finished buildings and supporting it is impracticable.
  • In one-, two- and multifamily dwellings, cable may run unsupported up to 4½ ft from the last support to a luminaire or equipment in an accessible ceiling.
  • For a device identified for use without a box, the cable must be secured within 12 in. of the wall opening, with a 12-in. loop or a 6-in. end left for future replacement.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process