NEC 240.87 · Commercial

Arc energy reduction for breakers of 1,200 A and up

Where a breaker's highest continuous trip setting is 1,200 A or more, the code requires one of seven arc energy reduction methods set below the available arcing current, with documentation and testing when first installed.

Diagram of the seven arc energy reduction methods for breakers with a highest trip setting of 1,200 A or more, plus documentation and on-site testing.
The trigger is the highest setting the breaker can be adjusted to, not the setting in use, so a breaker turned down below 1,200 A can still be covered. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

240.87 applies where a circuit breaker's highest continuous trip setting, whether its rating or the highest it can be adjusted to, is 1,200 A or more.

One of seven methods must be provided and set below the available arcing current: zone-selective interlocking; differential relaying; energy-reducing maintenance switching with a local status indicator; an energy-reducing active arc-flash mitigation system; an instantaneous trip setting below the arcing current; an instantaneous override below the arcing current; or an approved equivalent means. Temporarily adjusting the instantaneous trip setting does not count.

Documentation must show the breaker locations and that the method is set below the available arcing current, and be available to authorized persons. The method must be performance tested on site when first installed, by qualified persons following the manufacturer's instructions, using primary current injection or another approved method. A written record of the test must be available to your inspector.

On the job

  • A 1,200 A main breaker installed with no arc-energy method, documentation or test record is a common correction.
  • Using two to six smaller service disconnects (230.71) can keep each device under 1,200 A.
Closed gray commercial switchgear with a hazardous-voltage danger label on the door
Commercial switchgear with a danger label (representative stock photo).

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process