NEC 230.67 · Homes and commercial

Whole-house surge protection at the service

Services supplying homes, dorm units, hotel and motel guest rooms, and certain nursing-home sleeping rooms need a Type 1 or Type 2 surge-protective device at or next to the service equipment, rated at least 10 kA.

Diagram of a Type 1 or Type 2 surge protector, 10 kA minimum, mounted next to a home service panel, or at each downstream panel under the exception.
Replacing the service equipment on an existing home also brings in this rule, so a panel swap needs a Type 1 or Type 2 SPD rated 10 kA or more. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

A surge-protective device (SPD) is required on services that supply dwelling units, dormitory units, hotel and motel guest rooms and suites, and nursing-home and limited-care areas used only as patient sleeping rooms.

The SPD must be part of the service equipment or installed immediately next to it. It must be a Type 1 or Type 2 device, and its nominal discharge current rating (In) must be at least 10 kA.

When service equipment is replaced, all of 230.67 applies. That means replacing the service equipment on an existing home brings in the SPD requirement.

On the job

  • Replacing service equipment without adding an SPD is a common correction.
  • A Type 3 point-of-use device does not satisfy this rule.
  • An SPD rated below 10 kA nominal discharge current (In) does not meet the 2023 rule.
Three round electric meters on meter bases with conduit on an exterior block wall
Electric meters on an exterior wall (representative stock photo).

Exceptions that matter

  • The SPD may instead be installed at each next-level distribution equipment downstream toward the load, such as the interior panelboard fed by an exterior meter-main. If the service feeds more than one such piece of equipment, each one needs its own SPD.

What changed in 2023

The 2023 code expanded the rule from dwelling units only to dorms, hotel and motel rooms and nursing-home sleeping rooms, added the 10 kA minimum rating, and added companion rules for feeders (215.18) and outside feeders (225.42).

Related sections

  • NEC 215.18
  • NEC 225.42
  • NEC 230.82
  • NEC 242.9

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process