NEC 200.6 · Homes and commercial

How neutral wires must be identified

An insulated grounded (neutral) conductor 6 AWG or smaller must be identified by a continuous white or gray finish, or by three continuous white or gray stripes on insulation that is not green, with a few special cases.

Diagram of NEC 200.6 neutral markings, 6 AWG or smaller: white, gray, or three stripes on non-green insulation; re-marking in cables; gray may be hot.
In an existing building a gray wire may be a hot conductor, so test it before treating it as a neutral. Diagram: Farmer Works Electric, free to share under CC BY 4.0 · Download PNG · How to credit

What the code requires

Under 200.6(A), the insulation of a grounded conductor, usually called the neutral, sized 6 AWG or smaller must be identified by a continuous white outer finish, a continuous gray outer finish, or three continuous white or gray stripes running its entire length on insulation other than green. White or gray insulation with colored tracer threads that identify the manufacturer also qualifies.

Special cases in 200.6(A) cover single-conductor outdoor PV cable marked at its terminations, Type MI cable marked with an encircling white or gray marking at its terminations, fixture wire under 402.8, and aerial cable, which may be identified by a ridge.

Under 200.6(E), insulated neutrals inside multiconductor cables must be continuous white or gray, or have three white or gray stripes. Conductors 4 AWG and larger in cables may instead be identified as 200.6(B) allows. By exception, a conductor in a multiconductor cable may be re-identified as the neutral at its terminations, at the time of installation, with a distinctive white or gray marking or another equally effective means. An informational note warns that gray insulation may have been used for ungrounded (hot) conductors in older installations.

On the job

  • In existing buildings, a gray wire may be a hot conductor, so an electrician should verify it rather than assume it is a neutral.
  • Where a white or gray conductor in a cable is used as a hot, it must be re-identified as described in 200.7.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

Electrical work contracted under C K ELECTRIC · CSLB Lic. #354550 (C-10) · Farmer Works Electric license in process